Diesel Generators in Saudi Arabia — 10 kVA to 2500 kVA

Reliable Backup Power Solutions for Critical Operations

Diesel Generators in Saudi Arabia — 10 kVA to 2500 kVA

Diesel Generators – MHA Solutions Saudi Arabia (1)
Diesel Generators – MHA Solutions Saudi Arabia (2)
Diesel Generators – MHA Solutions Saudi Arabia (3)

Standby Power That Actually Starts

MHA Solutions supplies, installs, commissions and maintains diesel generator sets from 10 kVA to 2500 kVA across Saudi Arabia. We work with Perkins and Cummins engines, carry out the electrical works and fuel systems around the set ourselves, and support installations under maintenance contract once they are running. Our engineers have carried out generator testing at NEOM. A standby generator spends almost its entire life doing nothing. That is precisely the problem with it. Nobody notices a set that has quietly become unreliable — until the mains fails, and it either does not start at all, or starts, runs for four minutes, and shuts down on a fault that nobody knew was developing. Most generator failures are not dramatic. A battery that has lost cranking capacity in summer heat. A fuel supply that has degraded in storage. A coolant level nobody checked. An automatic transfer switch that has never actually been tested under load. Every one of those is preventable, and every one of them is found on a routine maintenance visit rather than during an outage. Specification matters just as much. A set sized only on running load will struggle or trip when a large motor starts, because starting current can be several times running current. A standby-rated set used as a prime power source will not last. And a generator installed without proper attention to ventilation, exhaust routing, fuel storage and earthing will underperform its nameplate regardless of how good the engine is. We size generators from a measured load study that accounts for motor starting, not from an equipment list. We specify the rating class against how the set will actually be used. We carry out the installation, the electrical works and the fuel system ourselves, so one team is accountable for the whole thing. And we maintain and load bank test the installation afterwards, because a generator that has never run at full load is an assumption rather than a backup. Our range covers 10 kVA sets for small commercial premises through to 2500 kVA plant for heavy industry and major infrastructure, for purchase and for rental.

Our Generator Services

01

Load Study and Sizing

We measure the actual load and, critically, the starting characteristics of the largest motor loads on the system. Motor starting is the factor most often underestimated: starting current can be several times running current, and a set sized only on running load will trip or suffer a voltage dip that takes other equipment out with it. The output is a sized specification with the rating class stated.

02

Supply and Delivery

Diesel generator sets from 10 kVA to 2500 kVA with Perkins and Cummins engines.

03

Installation and Electrical Works

Foundations and anti-vibration mounting, ventilation and heat rejection, exhaust routing and silencing, cabling and termination, earthing, changeover and distribution. Because we hold electrical contracting capability in-house, the machine and the installation around it are one scope rather than two contracts that meet somewhere in the middle.

04

Fuel Systems

Day tanks, bulk storage, transfer pumps, level monitoring, bunding and fuel polishing. Fuel is where a great many standby installations quietly fail, and it deserves more design attention than it usually gets.

05

Testing, Commissioning and Load Bank Testing

Commissioning covers functional testing, transfer and changeover verification, and load bank testing at rated capacity to confirm the set performs to specification under real load rather than on paper. We issue a full test report with the recorded voltage, frequency, current and temperature readings, which is normally required for project handover.

06

Preventive Maintenance and AMC

Scheduled servicing at manufacturer intervals, covering oil and filter changes, coolant condition and concentration, fuel system and water separator, air filtration, battery condition and cranking capacity, control panel and transfer testing, and a functional run under load. We recommend annual load bank testing for any critical standby installation.

07

Generator Rental

Short and long-term rental for construction projects, planned shutdowns, events, seasonal demand and emergency cover, including fuel systems, cabling, distribution and on-site support. See our dedicated generator rental page. Generator rental: 10 kVA – 3,000 kVA · minimum 1 day · fuel, cabling and on-site support included.

08

Overhaul, Upgrade and Relocation

Engine and alternator overhaul, control system upgrades on older sets, capacity uprating, relocation, and controlled decommissioning and removal.

Explore Our Other Power Products

Need Help with Engineering Solutions?

Talk to MHA Solutions for expert advice on Power, IT, and Security systems that fit your space. We cover Riyadh, Jeddah, Dammam, and other cities with custom plans.

Solutions Tailored to Your Infrastructure

Generator Types We Supply

Canopied and Silent Generators

Canopied and Silent Generators

An acoustic canopy encloses the set in sound-attenuating material and controls the exhaust and intake noise paths. This is what makes a generator acceptable next to a hospital ward, a hotel, a mosque or a residential block, and it is often a planning or municipal requirement rather than a preference. A canopy is not only about noise. It also protects the set from dust, sun and weather, which matters more here than in most markets.

Key Applications:

  • Hospital wards
  • Hotels
  • Mosques
  • Residential blocks

Available Specifications:

Acoustic canopy · dust, sun and weather protection

Request a Quote
Containerised Generators

Containerised Generators

A generator built into an ISO container or a purpose-made shelter, complete with ventilation, fuel system, control panel and distribution. Containerised sets suit remote sites, temporary installations, projects with no plant room, and large capacities where building a room around the machine is slower and more expensive than delivering it ready to run. They are also relocatable, which matters on a construction programme that moves.

Key Applications:

  • Remote sites
  • Temporary installations
  • Projects with no plant room
  • Large capacities

Available Specifications:

Ventilation, fuel system, control panel and distribution built in

Request a Quote
Open Skid Generators

Open Skid Generators

An open set on a base frame, for installation inside an existing plant room where the building provides the acoustic and weather protection. The plant room then has to do the work: ventilation sized for the heat rejection, exhaust routed correctly, and access for maintenance and eventual engine removal. We design that as part of the installation rather than leaving it to the builder.

Key Applications:

  • Existing plant rooms

Available Specifications:

Open set on a base frame

Request a Quote
Portable and Mobile Generators

Portable and Mobile Generators

Smaller sets on trailers or skids for site work, temporary events, emergency cover and jobs that move between locations. These are most often rented rather than bought.

Key Applications:

  • Site work
  • Temporary events
  • Emergency cover
  • Jobs that move between locations

Available Specifications:

Trailer or skid mounted

Request a Quote
Synchronised and Multi-Set Installations

Synchronised and Multi-Set Installations

Where one set cannot cover the load, or where the load must survive the loss of a single machine, multiple generators are run in synchronisation with load sharing between them. This also allows a set to be taken offline for maintenance without dropping the load — which is the only practical way to service a generator installation that cannot be shut down. Synchronisation requires proper control gear and commissioning. It is not something to add later as an afterthought.

Key Applications:

  • Loads one set cannot cover
  • Loads that must survive the loss of a machine
  • Servicing without dropping the load

Available Specifications:

Synchronisation with load sharing

Request a Quote
Automatic Transfer and AMF Control

Automatic Transfer and AMF Control

An Automatic Transfer Switch or Auto Mains Failure panel detects a mains failure, starts the generator, transfers the load, and reverses the sequence when the mains returns. This is what turns a generator into a backup system rather than a machine somebody has to go and start. The transfer arrangement is where a surprising number of installations fail, usually because it was never tested under real load after commissioning.

Key Applications:

  • Detects a mains failure
  • Starts the generator and transfers the load
  • Reverses the sequence when the mains returns

Available Specifications:

ATS or Auto Mains Failure panel

Request a Quote

Ideal For

Generator Applications by Industry

01

Healthcare

Hospitals and clinics where transfer time, reliability and regulatory compliance are all non-negotiable, and where the generator has to carry life-safety and critical care loads without interruption.

Key Benefits:

  • Transfer time
  • Reliability
  • Regulatory compliance
  • Life-safety and critical care loads
02

Construction & Infrastructure

Prime power for sites with no grid connection, and temporary power through the build programme. Rental usually makes more sense than purchase here, and sets need to be robust enough for site conditions.

Key Benefits:

  • Prime power with no grid connection
  • Temporary power through the build programme
  • Sets robust enough for site conditions
03

Water & Utilities

Treatment works, pumping stations and distribution control, frequently at unmanned remote sites where reliability and remote monitoring matter more than anything else.

Key Benefits:

  • Treatment works and pumping stations
  • Unmanned remote sites
  • Remote monitoring
04

Oil, Gas & Petrochemical

Process-critical and safety-related backup in high-temperature environments, with hazardous area classification driving specification where relevant.

Key Benefits:

  • Process-critical and safety-related backup
  • Hazardous area classification
05

Data Centres

Standby plant sized to carry the full IT and cooling load, commissioned with load bank testing, and often configured with multiple synchronised sets for redundancy.

Key Benefits:

  • Full IT and cooling load
  • Load bank testing at commissioning
  • Multiple synchronised sets
06

Telecom

BTS and transmission sites, often remote, often outdoors, where fuel logistics and unattended reliability are the governing constraints.

Key Benefits:

  • BTS and transmission sites
  • Fuel logistics
  • Unattended reliability
07

Commercial & Hospitality

Hotels, malls and office towers where acoustic performance and municipal noise limits shape the specification as much as the electrical requirement.

Key Benefits:

  • Acoustic performance
  • Municipal noise limits
08

Events

Temporary power for exhibitions, conferences and outdoor events, where silent running and fast mobilisation matter.

Key Benefits:

  • Silent running
  • Fast mobilisation

Generator Sizes We Supply — and What Each Range Suits

Capacity is only the starting point. The right set for a given load depends on rating class, motor starting characteristics and the environment it will run in — but this is the shape of the range.

01

10 – 50 kVA

Typical applications: Small offices, retail units, clinics, telecom cabinets, villas, site huts

What usually drives the specification: Physical footprint and noise. Usually canopied, often single-phase at the lower end.

02

60 – 150 kVA

Typical applications: Mid-size offices, small factories, schools, construction sites, mosques

What usually drives the specification: The most common band in the Kingdom. Automatic transfer switching is standard here.

03

200 – 500 kVA

Typical applications: Hospitals, hotels, small data centres, medium industrial, water pumping

What usually drives the specification: Motor starting almost always governs sizing rather than running load.

04

600 – 1000 kVA

Typical applications: Large industrial, water treatment works, large commercial developments

What usually drives the specification: Often multiple sets in synchronisation rather than one large machine.

05

1250 – 2500 kVA

Typical applications: Heavy industry, petrochemical, mining, major infrastructure projects

What usually drives the specification: Usually containerised or built into a purpose-designed plant room, with bulk fuel storage.

Standby, Prime and Continuous — Which Rating Do You Need?

A generator's rating describes how it is permitted to be used, not just how much power it can produce. The same physical set will carry a different kVA figure depending on the rating class, and using a set outside its class will shorten its life considerably.

01

Standby rating

Designed to run only when the mains fails, for a limited number of hours per year, at a varying load. This is the correct class for a building backup generator that may run for a few hours a month. Standby-rated sets carry the highest kVA figure of the three classes and have no overload capability.

02

Prime rating

Designed to run for an unlimited number of hours at a varying load, as the primary source of supply. This is what a remote site, a construction project or a facility without a reliable grid connection needs. Prime-rated sets are more heavily specified, carry a lower kVA figure than the same machine would as standby, and typically allow a limited overload for short periods.

03

Continuous rating

Designed to run indefinitely at a constant load — base load operation, or running in parallel with the grid. This carries the lowest kVA figure and the most conservative specification.

These classes are defined in ISO 8528-1, and every reputable manufacturer publishes ratings against them. The practical consequence is simple: if a supplier quotes you a headline kVA figure without stating the rating class, the quotation is incomplete. A 500 kVA standby set and a 500 kVA prime set are not the same machine at the same price.

Using a standby-rated set as a prime power source is one of the most common and most expensive specification errors we see. It works — right up until the engine reaches an early overhaul it should not have needed.

What Saudi Conditions Do to a Generator — and How We Specify For Them

A generator's nameplate rating is quoted at reference conditions. Real installations in the Kingdom rarely match them, and the difference between the nameplate figure and the deliverable output is not small.

01

Temperature derating

Engine and alternator output both fall as intake air temperature rises, because hotter air is less dense and carries less oxygen. Manufacturers publish derating curves for exactly this reason. A set specified against a nameplate figure without checking the curve against a 45°C summer ambient is not going to deliver what the drawing says it will. We size against the actual site condition, not the catalogue.

02

Altitude derating

Most of the Kingdom is low-lying enough that altitude is a minor factor, but not all of it. Installations in the Asir highlands around Abha and the surrounding region sit high enough that altitude derating is a real specification input, and it compounds with temperature rather than replacing it. This is routinely overlooked, and it is the sort of thing that only shows up when the set is asked for full output.

03

Air filtration and dust

Airborne dust is the most consistent maintenance burden on generators here. It loads air filters far faster than a temperate-climate service interval assumes, blocks radiator cores and reduces cooling capacity, and finds its way into places it should not. This drives filter specification, service intervals and enclosure design. A twelve-month service interval that works in Europe is not appropriate for an unsheltered industrial site in the Eastern Province.

04

Fuel storage and degradation

Diesel does not keep indefinitely. In warm conditions it degrades over months, and where water finds its way into a tank — through condensation, poor sealing or delivery — microbial growth follows. Heat accelerates both processes. The result on a standby set that runs a few hours a year is a tank of fuel that looks fine and blocks filters the moment it is genuinely needed. Fuel treatment, water separation, periodic polishing and tank maintenance are part of a real maintenance regime, not optional extras.

05

Coastal corrosion

On the Red Sea coast, salt-laden humid air attacks enclosures, radiators, exhaust systems and electrical terminations. An installation in Jeddah or Yanbu needs different corrosion protection from one in Riyadh, and treating the Kingdom as a single environment produces early failures.

06

Sandstorms

Intake protection and shutdown philosophy both need thinking through for sites exposed to sustained blowing sand, particularly for prime-rated sets that cannot simply be stopped.

Why a Standby Generator Needs Load Bank Testing

A diesel engine is designed to run under meaningful load. When a standby set is only ever exercised off-load or on a light building load — which describes most standby generators most of the time — the engine never reaches proper operating temperature and combustion is incomplete. Unburned fuel and soot accumulate in the cylinders, exhaust and turbocharger. The condition is known as wet stacking, and its symptoms are black exhaust, oil weeping from exhaust joints, falling performance and, eventually, engine damage.

The set will still start. It will still run. It simply will not deliver its rated output when the day comes that you need it.

Weekly no-load exercising, which many facilities do faithfully, does not solve this. It confirms that the engine starts. It tells you nothing about whether the set can carry its rated load, whether the alternator holds voltage and frequency under a step load, whether the cooling system copes at full output in summer, or whether the transfer arrangement actually works when it matters.

Load bank testing applies a controlled, measurable load so all of that can be verified and documented. For a critical standby installation we recommend annual testing at rated capacity, with a written report of the results. It is also a standard requirement for data centre commissioning and for handover on most infrastructure projects.

We provide load bank testing as part of our maintenance contracts and as a standalone service, with our own load banks and engineers.

Perkins and Cummins Generators

We supply diesel generator sets built around Perkins and Cummins engines. Both are supported worldwide, which is the practical reason they matter: parts and service expertise are available in the Kingdom, and a set that can be maintained locally is worth considerably more over fifteen years than one that cannot, whatever the purchase price comparison said.

Engine choice is only part of the specification. Alternator quality, control gear, and how the set is built and installed determine reliability just as much as the badge on the engine. We are happy to explain the trade-offs on a specific requirement rather than simply quoting a brand.

Generator Project Experience in Saudi Arabia

01

NEOM — Generator Testing & Commissioning

1.4 MW generator load bank testing and thermography, 2023, SAR 300,000. Read the NEOM case study.

Generator Supply, Installation and Service Across Saudi Arabia

We supply, install, service and rent generators Kingdom-wide from our base in Jeddah — including Riyadh, Dammam, Khobar, Jubail, Yanbu, Makkah, Madinah, Taif, Abha and remote industrial and infrastructure sites. Installation, commissioning, load bank testing, scheduled servicing and emergency callouts are carried out by our own engineers on site.

Diesel Generators — Frequently Asked Questions

What size generator do I need?+

Sizing depends on your total running load, the starting current of the largest motor on the system, whether the set is for standby or prime duty, and how much spare capacity you want for expansion. Motor starting is the factor most often underestimated — starting current can be several times running current, and a set sized only on running load will trip or produce a voltage dip that takes other equipment down with it. We carry out a load study before recommending a capacity.

What is the difference between standby, prime and continuous rated generators?+

A standby-rated set is designed to run only during a mains failure, for limited hours per year, at varying load. A prime-rated set is built to run unlimited hours at varying load as the primary supply. A continuous-rated set runs indefinitely at constant load. The same physical machine carries a different kVA figure in each class, so a quotation stating only a kVA number without the rating class is incomplete. Using a standby set as prime power is a common and expensive error.

Which generator brands do you supply?+

We supply sets built around Perkins and Cummins engines. Both have established parts and service support in the Kingdom, which matters far more over the life of the installation than the difference on the purchase invoice.

How much fuel will my generator use?+

Consumption is roughly proportional to load, and diesel engines are most efficient in the upper part of their load range rather than lightly loaded. Every manufacturer publishes a fuel consumption curve for the specific set at 25, 50, 75 and 100 per cent load, and that curve — not a rule of thumb — is what should drive your fuel storage sizing and running cost estimate. We provide the figures for the set we are quoting so you can plan tank capacity and refuelling logistics properly.

Do you supply silent or soundproof generators?+

Yes. Acoustic canopies are standard on most of our range and are frequently a municipal or planning requirement rather than a preference — particularly near hospitals, hotels, mosques and residential areas. A canopy also protects the set from dust and sun, which extends life in Saudi conditions.

Can you synchronise multiple generators?+

Yes. We supply and commission synchronisation and load-sharing systems for installations where a single set cannot cover the load, or where N+1 redundancy is required. Synchronisation also allows one set to be taken offline for servicing without dropping the load, which is often the only practical way to maintain an installation that cannot be shut down.

How often should a generator be serviced?+

At manufacturer-specified intervals — typically expressed in running hours or annually, whichever comes first. In Saudi conditions the dust load usually means air filtration needs attention more frequently than a temperate-climate interval assumes. A service should cover oil and filters, coolant condition, fuel system and water separator, air filtration, battery cranking capacity, control panel and transfer testing, and a functional run under load.

Why does my generator need load bank testing if we exercise it weekly?+

Weekly off-load exercising confirms that the engine starts. It does not confirm that the set can carry its rated load, that the alternator holds voltage and frequency under a step load, that cooling copes at full output in summer, or that the transfer arrangement works. Running a diesel engine repeatedly at light load also causes wet stacking, where unburned fuel accumulates in the exhaust system and degrades performance. Annual load bank testing at rated capacity addresses both, and produces a documented result.

How long can diesel be stored before it degrades?+

Untreated diesel degrades over a period of months, and heat accelerates it. Where water enters a tank through condensation or delivery, microbial growth follows — and warm, humid conditions make that considerably worse. On a standby set that runs a few hours a year, the result is a tank of fuel that looks perfectly normal and blocks filters the moment it is genuinely needed. Fuel treatment, water separation and periodic polishing should be part of the maintenance regime.

Do generators need derating in Saudi Arabia?+

Yes, and it is regularly missed. Output falls as intake air temperature rises, so a set specified against its nameplate without checking the manufacturer's derating curve against a 45°C ambient will not deliver what the drawing assumes. Altitude adds a further reduction, which is minor across most of the Kingdom but genuinely significant in the Asir highlands around Abha, where it compounds with the temperature effect. We size against actual site conditions rather than catalogue reference conditions.

Get a Generator Specification and Quote

Send us your load schedule, a single-line diagram, or a description of the site and what needs backing up. We will arrange a survey where it is needed and return a sized specification with the rating class stated, a costed proposal, and a maintenance option.

Our Story

One Engineering Partner for Power, IT, Security and Electrical Works

Most facilities in the Kingdom deal with separate suppliers for power, IT and security, then discover the gaps between them at the worst possible moment. The UPS vendor points at the electrical contractor. The IT supplier says the rack was never their scope. Nobody owns the problem.

MHA Solutions covers all four disciplines with one engineering team. That means one point of accountability for the UPS, the distribution board feeding it, the server rack it protects and the access control system on the door of the room.

We work with industrial plants, healthcare facilities, government entities, data centres, telecom operators and major infrastructure contractors across Saudi Arabia. Our engineers handle the full lifecycle: site survey and load study, system design and specification, supply, installation, testing and commissioning, and ongoing maintenance under contract.

Equipment that performs well in a temperate climate does not always survive a Saudi plant room. Ambient temperatures above 45°C shorten battery life, airborne dust clogs filters and cooling paths, and salt-laden humidity on the Red Sea coast attacks enclosures and terminations. We specify for those conditions from the start, because replacing equipment early is far more expensive than sizing it correctly on day one.

Discover Our Journey

100+

Happy customers

50+

Brand partnerships

20+

Years in business

4

Countries Served

Welcome to MHA Solutions
20+
Years of Excellence

OUR SERVICES

Built for power, security and IT infrastructure

Explore engineered solutions for mission-critical environments across power, IT and security.

All

Engineering reliable infrastructure for critical facilities.

Power

Engineering reliable infrastructure for critical facilities.

Security

Engineering reliable infrastructure for critical facilities.

IT

Engineering reliable infrastructure for critical facilities.

UPS Systems

Power Systems

UPS Systems

Reliable continuous power protection for mission critical operations.

Explore
Diesel Generators

Power Systems

Diesel Generators

Dependable backup power engineered for industrial and commercial use.

Explore
Voltage Stabilizers (AVR)

Power Systems

Voltage Stabilizers (AVR)

Precision automatic voltage stabilization for sensitive equipment.

Explore
Transformers

Power Systems

Transformers

Efficient power distribution and voltage conversion for industrial facilities.

Explore
Electrical Contracting

Power Systems

Electrical Contracting

Professional electrical contracting and installation services for critical infrastructure.

Explore
Load Bank Rental & Testing

Power Systems

Load Bank Rental & Testing

Resistive and reactive load bank hire for generator, UPS and data centre commissioning.

Explore
UPS Batteries & DC Systems

Power Systems

UPS Batteries & DC Systems

VRLA, lithium and industrial DC battery systems engineered for Saudi heat conditions.

Explore
UPS Rental

Power Systems

UPS Rental

Short and long-term UPS rental for shutdowns, data centre maintenance, events and construction.

Explore
Generator Rental

Power Systems

Generator Rental

Diesel generator rental for construction, events, shutdowns and emergency backup.

Explore
CCTV Systems

Security

CCTV Systems

High-definition video surveillance & AI analytics for critical infrastructures.

Explore
Access Control Systems

Security

Access Control Systems

Intelligent biometric and RFID entry identity management systems.

Explore
Cyber Security Services

Security

Cyber Security Services

Next-generation firewalls and advanced endpoint protection platforms.

Explore
Biometric Attendance Systems

Security

Biometric Attendance Systems

Fingerprint and face recognition time-attendance systems with payroll integration.

Explore
Enterprise Servers

IT Infrastructure

Enterprise Servers

High-performance computing and data management architectures.

Explore
Server Racks & PDUs

IT Infrastructure

Server Racks & PDUs

Structurally superior, thermally optimized rack containment systems.

Explore
Network Switches & Solutions

IT Infrastructure

Network Switches & Solutions

High-speed, zero-latency core and edge switching fabrics.

Explore
Workstations & Business Laptops

IT Infrastructure

Workstations & Business Laptops

High-performance computing power for CAD, engineering and data-intensive workloads.

Explore
Structured Cabling & Fiber Optic

IT Infrastructure

Structured Cabling & Fiber Optic

End-to-end structured cabling, data center build and IT lifecycle management.

Explore
Data Centre Solutions

IT Infrastructure

Data Centre Solutions

Turnkey data centre build, hot and cold aisle containment and legacy migration.