Reliable Power Protection Solutions for Mission Critical Applications
MHA Solutions supplies, installs, commissions and maintains uninterruptible power supply systems from 1 kVA to over 800 kVA across Saudi Arabia. We are authorised partners for Schneider Electric and Reliability Power Systems, and our engineers have delivered UPS work on projects including Riyadh Metro, the National Water Company plant at Taif, and Maaden industrial facilities. A UPS is the last line of defence between a mains disturbance and everything downstream of it. When the grid dips, spikes or fails, the UPS carries the load without a break in supply until either the mains returns or a generator picks up. That job sounds simple. Specifying the right system for it is not. A UPS sized on a nameplate total will trip when a motor starts. An oversized unit runs inefficiently and costs more than it needed to. A system specified for a temperate climate will lose battery capacity years early in a Saudi plant room. And a UPS installed without proper attention to earthing, distribution and bypass arrangements can introduce the very risks it was bought to remove. We size UPS systems from a measured load survey rather than an equipment list. We specify for the actual environment — ambient temperature, ventilation, dust load, coastal exposure, and the quality of the incoming supply. We carry out the installation and the electrical works around it ourselves, so responsibility for the whole installation sits in one place. And we maintain the system afterwards, because a UPS that has never been tested under load is an assumption rather than a protection. Our range runs from a 1 kVA unit protecting a single communications cabinet to systems above 800 kVA supporting data centres, water treatment plants and industrial process control. We supply for purchase and for rental, and we take on maintenance contracts for systems we did not originally install.
We measure the actual load rather than adding up nameplate ratings, because the two are rarely the same. The survey covers running load, the starting characteristics of the largest motor loads, power factor, crest factor, planned expansion and the runtime you actually need. The output is a sized specification you can put out to tender, not a sales quotation.
We supply UPS systems from 1 kVA to over 800 kVA through authorised channels, which means genuine equipment, valid manufacturer warranty and access to factory technical support and spares.
Because we hold electrical contracting capability in-house, we can carry out the installation around the UPS as well as the UPS itself, distribution board modifications, cabling and termination, earthing arrangements, bypass provision and generator changeover. That removes the gap between an equipment supplier and a separate contractor, which is where a surprising number of installation problems originate.
Commissioning covers functional testing, transfer and bypass verification, battery autonomy testing at the design load, and thermal inspection of connections under load. We issue a commissioning report with the recorded results, which is usually required for project handover and is worth having regardless.
Most UPS failures announce themselves long before they happen, if anyone is looking. Our maintenance visits cover battery health and impedance testing, thermal imaging of terminations, internal cleaning and filter checks, capacitor and fan condition, firmware and event log review, and a functional discharge test. We recommend two visits a year for business-critical systems and quarterly for installations in hot or dusty industrial environments.
Battery capacity degrades gradually and invisibly. A bank that looks healthy and shows a normal float voltage can fail to deliver half its rated autonomy. We carry out impedance testing and timed discharge testing to establish actual remaining capacity, and we supply, install and commission replacement banks, including removal and compliant disposal of the old cells.
We rent UPS systems for planned shutdowns, data centre maintenance windows, construction and fit-out projects, events, and emergency cover while a permanent system is repaired or replaced. Rental units are tested before dispatch, and delivery, installation, commissioning and collection are included. UPS rental: 1 kVA – 2,000 kVA · minimum 1 day · delivery, installation and commissioning included. See UPS rental.
Facilities move, loads change and systems reach end of life. We handle UPS relocation, capacity upgrades, controlled decommissioning and removal, including safe handling and disposal of battery banks.
Talk to MHA Solutions for expert advice on Power, IT, and Security systems that fit your space. We cover Riyadh, Jeddah, Dammam, and other cities with custom plans.
.png)
In an online double-conversion UPS the incoming AC supply is rectified to DC and then inverted back to AC, and the load is fed from the inverter at all times. Mains power never reaches your equipment directly. That gives complete isolation from voltage sags, surges, frequency drift, harmonics and transients — and a transfer time of zero when the supply fails, because nothing transfers. The load was already on the inverter. This is the correct topology wherever an interruption has real consequences: data centres and server rooms, hospital imaging and theatre equipment, industrial process control, SCADA and telecom infrastructure. It is also what to specify where the incoming supply is poor, which describes a great many industrial sites in the Kingdom. Under IEC 62040-3 this classification is VFI — voltage and frequency independent. More on online UPS.
IEC 62040-3 VFI · zero transfer time
.png)
A line-interactive UPS corrects voltage sags and swells using an autotransformer, without drawing on the battery. It switches to battery only when the supply fails outright, with a transfer time typically in the low milliseconds — fast enough for IT equipment with switch-mode power supplies, but not fast enough for everything. This topology suits office IT, networking cabinets, point-of-sale systems, CCTV recording equipment and small server installations. It costs less than online double-conversion and runs at higher efficiency, which matters when a site has many small units rather than one large one. It is not the right choice for medical equipment, motor loads or industrial control systems. If you are being offered line-interactive for any of those, ask why.
Transfer time in the low milliseconds
.png)
A modular UPS is built from hot-swappable power modules within a common frame. You install the capacity you need today and add modules as the load grows, instead of buying for a load you might have in five years and running at twenty per cent for the first three. The second advantage is redundancy. In an N+1 configuration one module can fail or be removed for service while the others continue to carry the full load, and modules can be replaced without shutting the system down or transferring to bypass. Modular systems suit data centres, colocation facilities and any installation where the load will grow or where availability requirements make a single-unit failure unacceptable. More on modular UPS.
Hot-swappable modules · N+1 redundancy
.png)
Industrial UPS systems are built for conditions that shorten the life of a commercial-grade unit: sustained high ambient temperature, airborne dust and particulates, vibration, and continuous duty with no convenient maintenance window. The specification differences are real rather than marketing. Enclosure protection ratings are higher, cooling is designed for sustained high ambient instead of an air-conditioned room, components are derated, and the units are built to be serviced in place rather than swapped out. We supply industrial UPS for manufacturing plants, petrochemical facilities, substations, water treatment works and mining operations. Where the installation sits in or near a classified hazardous area, that has to be part of the specification from the beginning, not an afterthought at commissioning. More on industrial UPS.
Higher enclosure protection · derated components
.png)
Some installations have no plant room at all. Telecom sites, remote pumping stations, roadside cabinets and equipment along transport corridors need a UPS that lives outdoors. That means a sealed enclosure with an appropriate ingress protection rating, active thermal management, and protection against dust and wind-blown sand. On the Red Sea coast it also means corrosion resistance suited to salt-laden air. Battery selection matters more in these installations than anywhere else, because an outdoor cabinet in summer runs considerably hotter than an indoor plant room, and battery life is measured against that temperature rather than the datasheet's.
Sealed enclosure · active thermal management
Online double-conversion or modular systems with N+1 redundancy, battery autonomy sized to bridge to generator start, and load bank testing at commissioning to verify the design under real load rather than on paper.
Imaging, theatre, laboratory and critical care equipment cannot tolerate a transfer gap. Specification here is driven by the equipment manufacturer's requirements and by hospital electrical standards, and the maintenance regime matters as much as the initial installation.
Treatment plants, pumping stations and distribution control systems, often at unmanned sites with limited access. We have delivered UPS infrastructure for the National Water Company.
Process control, safety instrumented systems and substation auxiliaries in high-temperature environments, with hazardous area classification driving specification where relevant.
Base stations, transmission sites and exchange equipment, frequently outdoors and frequently remote, where battery performance in heat is the governing factor.
Production line control, automation and instrumentation, where a momentary interruption can mean a spoiled batch or a line restart measured in hours. We support Maaden industrial facilities.
Transport, public buildings and national infrastructure. Our engineers carried out power system testing on Riyadh Metro: UPS T&C with load banks, all RMTC stations, 2025–2026, SAR 1 million.
Undersizing and oversizing are both expensive, in different ways. These are the factors that determine the answer.
Nameplate ratings state what equipment can draw under worst-case conditions, not what it does draw. Summing nameplates typically produces a figure well above reality and leads to an oversized, inefficient and unnecessarily costly system. A measured load reading over a representative period is the better starting point.
Modern IT loads with switch-mode power supplies behave differently from motor loads. A UPS rated in kVA may deliver considerably less usable kW depending on the load's power factor, and non-linear loads draw current in short high peaks that the system has to handle without distortion.
This is the factor most often missed. A generator or UPS sized only on running load will struggle or trip when a large motor or compressor starts. Starting current can be several times running current, and the system has to ride through it.
Runtime requirement depends on what the UPS is bridging to. If a generator is present and starts reliably, a few minutes of autonomy is usually sufficient. If there is no generator, and the requirement is to keep running for an hour, the battery bank changes size dramatically — and at that point a UPS plus generator is almost always the better engineering and commercial answer than a very large battery installation.
Whether the requirement is N, N+1 or 2N changes both the capacity and the topology. This is a business decision about acceptable downtime as much as a technical one.
Twenty to thirty per cent headroom is a common allowance, but a modular system may serve you better than buying spare capacity up front and running at low load for years.
Equipment that performs reliably in a temperate climate does not automatically survive a Saudi installation. These are the factors that change the specification.
This is the single biggest issue, and the one most often ignored at purchase. VRLA battery life is rated at 25°C, and a widely used engineering rule of thumb is that float life roughly halves for every 10°C of sustained temperature above that. A bank rated for five years in a climate-controlled room may deliver a fraction of that in an unconditioned plant room running at 40°C or above. The battery does not announce this. It simply fails to deliver its rated autonomy when it is finally called upon. Where plant room cooling cannot be guaranteed, that has to be reflected in the battery technology chosen, the replacement interval planned, and the testing schedule.
The UPS itself is affected too. Manufacturers specify a maximum operating temperature and a derating curve above it, and a unit installed in a room that regularly exceeds that figure is not delivering its nameplate capacity. Ventilation and heat rejection need to be part of the design conversation, not discovered in July.
Airborne dust clogs filters and heat-exchange paths, and fine particulate accumulating on boards degrades cooling and eventually causes tracking faults. This drives both enclosure selection and maintenance frequency — a quarterly interval in an industrial environment is not conservative, it is realistic.
Along the Red Sea coast, salt-laden humid air attacks enclosures, terminations and exposed contacts. An installation in Jeddah or Yanbu has different corrosion requirements from one in Riyadh, and the specification should reflect that rather than treating the Kingdom as a single environment.
Voltage fluctuation and harmonic distortion vary considerably between well-served urban areas and industrial or remote sites. Where the supply is poor, online double-conversion is the appropriate topology, and input harmonic performance becomes a specification point rather than a footnote — particularly where the UPS is fed from a generator.
A UPS and a generator have to be sized as a pair. A generator that is undersized relative to the UPS input, or a UPS whose input harmonics the generator cannot tolerate, produces a system that works on mains and fails on backup. We size and test the combination together.
We are authorised partners for Schneider Electric and Reliability Power Systems. Buying through an authorised channel is not a formality — it determines whether the warranty is valid, whether you get factory technical support when a fault is unclear, and whether a critical spare arrives in hours or in weeks. Grey-market UPS equipment is cheaper on the invoice and considerably more expensive the first time it fails.
We supply, install and service UPS systems Kingdom-wide from our base in Jeddah — including Riyadh, Dammam, Khobar, Jubail, Yanbu, Makkah, Madinah, Taif and remote industrial and infrastructure sites. Maintenance visits, commissioning and emergency callouts are carried out by our own engineers on site.
Sizing starts with a measured load rather than a total of nameplate ratings, which usually overstates the real figure. We then account for power factor, the starting current of the largest motor loads, the runtime you need, whether a generator is present to bridge to, and how much growth to allow — commonly twenty to thirty per cent. Our engineers carry out a load survey on site and issue a sized specification.
An online double-conversion UPS feeds the load from its inverter at all times, giving complete isolation from mains disturbances and no transfer time. A line-interactive UPS regulates voltage without using the battery and switches to battery only on a full outage, with a transfer time of a few milliseconds. A modular UPS is built from hot-swappable modules so capacity and redundancy can be scaled without replacing the system. Online suits critical loads, line-interactive suits general IT, and modular suits installations that will grow.
Runtime depends on battery capacity and how heavily the UPS is loaded. A standard configuration commonly gives somewhere between five and thirty minutes at full load, which is enough to ride through a short outage or transfer cleanly to a generator. Longer autonomy is achieved with additional battery cabinets. If the requirement runs to hours rather than minutes, a UPS paired with a generator is almost always a better answer than a very large battery bank.
Yes. Industrial UPS systems are specified for high ambient temperature, dust, vibration and continuous duty — conditions in which a commercial-grade unit will fail early. We supply industrial UPS for manufacturing plants, petrochemical facilities, substations, water treatment works and mining operations, with enclosure rating and derating specified against the actual site conditions rather than an assumed office environment.
Yes. We rent UPS systems for planned shutdowns, data centre maintenance windows, construction and fit-out projects, events and emergency cover. Units are tested before dispatch, and delivery, installation, commissioning and collection are included. UPS rental: 1 kVA – 2,000 kVA · minimum 1 day · delivery, installation and commissioning included.
Twice a year is a reasonable baseline for business-critical systems, and quarterly is more realistic for installations in hot or dusty industrial environments. A service visit should cover battery health and impedance testing, thermal inspection of connections, internal cleaning and filter checks, capacitor and fan condition, firmware and event log review, and a functional discharge test.
Less than the datasheet suggests, unless the plant room is properly cooled. VRLA batteries are rated at 25°C, and a widely used rule of thumb is that float life roughly halves for every 10°C of sustained temperature above that. A bank rated for five years may deliver considerably less in an unconditioned room. This is why we recommend capacity testing rather than relying on age alone — a battery can look fine and still fail to deliver its rated autonomy.
Yes. We take on maintenance contracts for existing installations regardless of who originally supplied them. The first step is a condition assessment covering the UPS, the battery bank and the surrounding electrical infrastructure, after which we propose an appropriate maintenance schedule.
It should, but only if the two were sized as a pair. Problems arise when the generator is undersized relative to the UPS input, or when the generator cannot tolerate the harmonic current the UPS draws — producing a system that works on mains and fails on backup, which is the worst possible outcome. We size and commission the combination together, and we can load bank test it to confirm the design holds under real load.
Send us your load schedule, a single-line diagram, or simply a description of what needs protecting and where. We will arrange a site survey where it is needed and come back with a sized specification and a costed proposal.
Most facilities in the Kingdom deal with separate suppliers for power, IT and security, then discover the gaps between them at the worst possible moment. The UPS vendor points at the electrical contractor. The IT supplier says the rack was never their scope. Nobody owns the problem.
MHA Solutions covers all four disciplines with one engineering team. That means one point of accountability for the UPS, the distribution board feeding it, the server rack it protects and the access control system on the door of the room.
We work with industrial plants, healthcare facilities, government entities, data centres, telecom operators and major infrastructure contractors across Saudi Arabia. Our engineers handle the full lifecycle: site survey and load study, system design and specification, supply, installation, testing and commissioning, and ongoing maintenance under contract.
Equipment that performs well in a temperate climate does not always survive a Saudi plant room. Ambient temperatures above 45°C shorten battery life, airborne dust clogs filters and cooling paths, and salt-laden humidity on the Red Sea coast attacks enclosures and terminations. We specify for those conditions from the start, because replacing equipment early is far more expensive than sizing it correctly on day one.
Discover Our JourneyHappy customers
Brand partnerships
Years in business
Countries Served

Explore engineered solutions for mission-critical environments across power, IT and security.
Engineering reliable infrastructure for critical facilities.
Engineering reliable infrastructure for critical facilities.
Engineering reliable infrastructure for critical facilities.
Engineering reliable infrastructure for critical facilities.